H07V-R | PVC Insulated Single Core Wire
Item descriptions
| Application: | For indoor fixed installations in dry locations, in switchboards and distributors, installed in surface mounted or embedded conduits, or on suitably objects. |
| Construction: | 1.....stranded bare copper, compacted 2.....PVC insulation |
| Standards: | DIN VDE 0281-3 DIN EN 60228 Class 2 (construction) |
| Nominal voltage Uo/U | [V] | 450 / 750 Volt | |
| Test voltage | [V]AC | 2500 | |
| Temperature range | in motion | +5°C till +70°C | |
| Operating temperature | short circuit | °C | 160 |
| Short circuit time | max. | [sec] | 5 |
| Bending radius | min. | x diameter | 4 |
| Flammability | standard | EN 60332-1-2 |
| Nominal cross section mm² | Colours | Copper figure kg/km | Cond. construction (appr. value) mm | Overall diameter appr. mm | Weight appr. kg / km |
| 6 | bk/bl | 57,60 | 7 X 1,05 | 5,0 | 66 |
| gr | 57,60 | 7 X 1,05 | 5,0 | 66 | |
| 10 | bk/bl/br | 96,00 | 7 X 1,35 | 6,0 | 110 |
| gr | 96,00 | 7 X 1,35 | 6,0 | 110 | |
| 16 | bk/bl | 153,60 | 7 X 1,70 | 7,0 | 170 |
| br/gr | 153,60 | 7 X 1,70 | 7,0 | 170 | |
| 25 | bk | 240,00 | 7 X 2,13 | 9,0 | 270 |
| bl/br/gr | 240,00 | 7 X 2,13 | 9,0 | 270 | |
| 35 | bk | 336,00 | 7 X 2,52 | 10,0 | 360 |
| bl/br/gr | 336,00 | 7 X 2,52 | 10,0 | 360 | |
| 50 | bk | 480,00 | 19 X 1,83 | 11,0 | 530 |
| bl/gr | 480,00 | 19 X 1,83 | 11,0 | 530 | |
| 70 | bk | 672,00 | 19 X 2,17 | 14,0 | 740 |
| bl/gr | 672,00 | 19 X 2,17 | 14,0 | 740 | |
| 95 | bk | 912,00 | 19 X 2,52 | 15,0 | 1.000 |
| gr | 912,00 | 19 X 2,52 | 15,0 | 1.000 | |
| 120 | bk | 1.152,00 | 37 X 2,03 | 18,0 | 1.250 |
| gr | 1.152,00 | 37 X 2,03 | 18,0 | 1.250 | |
| 150 | bk | 1.440,00 | 37 X 2,27 | 19,0 | 1.580 |
| gr | 1.440,00 | 37 X 2,27 | 19,0 | 1.580 | |
| 185 | bk | 1.776,00 | 37 X 2,52 | 21,0 | 1.930 |
| gr | 1.776,00 | 37 X 2,52 | 21,0 | 1.930 | |
| 240 | bk | 2.304,00 | 61 X 2,24 | 23,0 | 2.500 |
| gr | 2.304,00 | 61 X 2,24 | 23,0 | 2.500 | |
| 300 | bk | 2.880,00 | 61 X 2,50 | 29,6 | 3.130 |